EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Appendix 4 PID Operation Program Examples

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2058
APPX
Appendix 4 PID Operation Program Examples
Appendix 4 PID Operation Program Examples
This section provides examples of PID operation programs where the PID operation instruction is used.
The following system configuration is used.
X2: Auto tuning command
X3: PID control command
Y20: Error indication
Y21: Heater output
Operation of output value
PID control
Auto Tuning: 90% of maximum output
Item During auto tuning During PID control
Set value (s1) 500 (+50)500 (+50)
Control data Sampling time (T
S
) (s3) 3000ms 500ms
Input filter () (s3)+2 70% 70%
Derivative gain (K
D
) (s3)+5 0% 0%
Output upper limit value (s3)+22 2000 (2 seconds) 2000 (2 seconds)
Output lower limit value (s3)+23 0 0
Action setting (ACT) Input variation alarm Bit 1 of (s3)+1 Disabled Disabled
Output variation alarm Bit 2 of (s3)+1 Disabled Disabled
Output upper/lower
limit value setting
Bit 5 of (s3)+1 Enabled Enabled
Output value (d) 1800 According to operation
PV
MV
PV
MV
CPU module
D/A
converter
module
A/D
converter
module
Sensor
Control target
PID operation
ONONON
OFF
ON ON
2000ms 2000ms
D502 × 1ms
2000ms
2000ms 2000ms2000ms
1800ms 1800ms 1800ms

Table of Contents