1638
18 CC-LINK IE FIELD NETWORK INSTRUCTIONS
18.9 Sending an SLMP Frame
18.9 Sending an SLMP Frame
J(P).SLMPREQ, G(P).SLMPREQ
These instructions send an SLMP frame to the SLMP-compatible device in the same network. Data of the target station can
be read/written and operated.
■Execution condition
■Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
• The RnENCPU (network part), RJ71GF11-T2, and RJ71EN71 with firmware version "18" or later support these instructions. (Use an engineering tool with
version "1.035M" or later.)
Ladder ST
ENO:=J_SLMPREQ(EN,J,s1,s2,d1,d2);
ENO:=JP_SLMPREQ(EN,J,s1,s2,d1,d2);
ENO:=G_SLMPREQ(EN,U,s1,s2,d1,d2);
ENO:=GP_SLMPREQ(EN,U,s1,s2,d1,d2);
FBD/LD
Instruction Execution condition
J.SLMPREQ
G.SLMPREQ
JP.SLMPREQ
GP.SLMPREQ
Operand Description Range Data type Data type (label)
(J/U) J(P).SLMPRE
Q
(J): Own station network number 1 to 239 16-bit unsigned binary ANY16
G(P).SLMPRE
Q
(U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own
node
00H to FEH 16-bit unsigned binary ANY16
(s1) Own station start device where control data is
stored
Refer to the control data. Device name ANY16
*1
(s2) Own station start device where request data is
stored
Device name ANY16
*1
(d1) Own station start device for storing response data Device name ANY16
*1
(d2) Device of the own station, which turns on for one
scan upon completion of the instruction. When the
instruction completes with an error, (d2)+1 also
turns on.
Bit ANYBIT_ARRAY
(Number of elements:
2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(J/U) (s1) (s2) (d1) (d2)