7 APPLICATION INSTRUCTIONS
7.12 Data Control Instructions
875
7
Scaling 16-bit binary data (XY coordinates)
SCL2(P)(_U)
These instructions scale the scaling conversion data (16-bit data) on the basis of the specified input value (XY coordinates).
Execution condition
Setting data
Description, range, data type
*1 The number of coordinate points in (s2) is represented in 16-bit unsigned binary.
*2 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Applicable devices
Ladder ST
ENO:=SCL2(EN,s1,s2,d);
ENO:=SCL2P(EN,s1,s2,d);
ENO:=SCL2_U(EN,s1,s2,d);
ENO:=SCL2P_U(EN,s1,s2,d);
FBD/LD
Instruction Execution condition
SCL2
SCL2_U
SCL2P
SCL2P_U
Operand Description Range Data type Data type (label)
(s1) SCL2(P) Input value to be scaled or the device containing
the input value
-32768 to 32767 16-bit signed binary ANY16_S
SCL2(P)_U 0 to 65535 16-bit unsigned binary ANY16_U
(s2) SCL2(P) Start device containing scaling conversion data 16-bit signed binary
*1
ANY16_S
*2
SCL2(P)_U 16-bit unsigned binary
*1
ANY16_U
*2
(d) SCL2(P) Device for storing the output value controlled by
scaling
16-bit signed binary ANY16_S
SCL2(P)_U 16-bit unsigned binary ANY16_U
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s1) 
(s2)  
(d)  
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s1) (s2) (d)
EN ENO
ds1
s2