19 CC-LINK INSTRUCTIONS
19.5 Reading Data from the Automatic Update Buffer
1657
19
19.5 Reading Data from the Automatic Update Buffer
G(P).RIFR
These instructions read data from the automatic update buffer or random access buffer. The instructions can be used for
communications with a module having the automatic update buffer such as AJ65BT-R2N.
Execution condition
Setting data
Description, range, data type
*1 Value that was set in the CC-Link configuration window of the engineering tool.
*2 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Ladder ST
ENO:=G_RIFR(,ENU,s1,s2,n,d);
ENO:=GP_RIFR(EN,U,s1,s2,n,d);
FBD/LD
Instruction Execution condition
G.RIFR
GP.RIFR
Operand Description Range Data type Data type (label)
(U) Start I/O number (first three digits in four-digit
hexadecimal representation) of a module
00H to FEH 16-bit unsigned binary ANY16
(s1) If data is read from an automatic update buffer: Station
number of intelligent device station
1 to 64 16-bit unsigned binary ANY16
If data is read from a random access buffer: Specifies
the random access buffer.
00FFH 16-bit unsigned binary ANY16
(s2) Offset value from the start of the automatic update or
random access buffer that has been assigned to the
target station
0 to parameter set value
*1
16-bit unsigned binary ANY16
(d) Start device for storing the read data Device name ANY16
*2
(n) Number of read points 1 to 4096 16-bit unsigned binary ANY16
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(U) (s1) (s2) (d) (n)
EN ENO
U
s1
d
s2
n