15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1469
15
Writing data to the programmable controller on another station
JP.WRITE, GP.WRITE
These instructions write data to a device in the programmable controller of another station (in units of words).
■Execution condition
■Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
*2 For the specifications of the string data to be specified, refer to the following.
Page 1452 Specifications of character string data specified by link dedicated instructions
Ladder ST
ENO:=JP_WRITE(EN,J,s1,s2,d1,d2);
ENO:=GP_WRITE(EN,U,s1,s2,d1,d2);
FBD/LD
Instruction Execution condition
JP.WRITE
GP.WRITE
Operand Description Range Data type Data type (label)
(J/U) JP.WRITE (J): Own station network number 1 to 239 16-bit unsigned binary ANY16
GP.WRITE (U): Start I/O number (first three digits in four-digit
hexadecimal representation) of own station or own
node
00H to FEH 16-bit unsigned binary ANY16
(s1) Own station start device where control data is
stored
Refer to the control data. Device name ANY16
*1
(s2) Own station start device containing write data Device name ANY16
*1
(d1) Target station start device to which data is to be
written
String
*2
ANYSTRING_SINGLE
*2
(d2) Device of the own station, which turns on for one
scan upon completion of the instruction.
When the instruction completes with an error,
(d2)+1 also turns on.
Bit ANYBIT_ARRAY
(Number of elements: 2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(J/U) (s1) (s2) (d1) (d2)