EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Reading Data from the Data Memory

Mitsubishi Electric MELSEC iQ-R Series
2110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
594
7 APPLICATION INSTRUCTIONS
7.6 Reading/Writing Data Instructions
Reading data from the data memory
S(P).DEVLD
These instructions read data from the device data storage file in data memory.
Execution condition
Setting data
Descriptions, ranges, and data types
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Applicable devices
Ladder ST
ENO:=S_DEVLD(EN,s,n,d);
ENO:=SP_DEVLD(EN,s,n,d);
FBD/LD
Instruction Execution condition
S.DEVLD
SP.DEVLD
Operand Description Range Data type Data type (label)
(s) Read offset of device data storage file (specified in units of
16-bit words)
0 to 524287 32-bit unsigned binary ANY32
(d) Device for storing the data that has been read Word ANY16
*1
(n) Number of read points 1 to 65535 16-bit unsigned binary ANY16
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s)  
(d)  
(n)  
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s) (d) (n)
EN ENO
sd
n

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series

Related product manuals