2084
APPX
Appendix 7 List of Loop Tag Memory Areas Used by Process Control Instructions
I-PD control (SIPD), blend PI control (SBPI)
Offset Instruction
used
Item Name Recommended
range
Data type Set by
SIPD SBPI
+1 Shared
among the
instructions
MODE Control mode 0 to FFFFH 16-bit unsigned
binary
User/system User/system
+3 ALM Alarm detection 0 to FFFFH 16-bit unsigned
binary
User/system User/system
+4 INH Disable alarm
detection
0 to FFFFH 16-bit unsigned
binary
User/system User/system
+10
+11
S.PHPL PV Process value RH to RL Single-precision real
number
System System
+12
+13
S.OUT1 MV Manipulated value -10 to 110 [%] Single-precision real
number
User/system User/system
+14
+15
S.IPD/S.BPI SV Set value RL to RH Single-precision real
number
User User
+16
+17
S.IPD/S.BPI DV Deviation -110 to 110 [%] Single-precision real
number
System System
+18
+19
S.OUT1 MH Output upper limit
value
-10 to 110 [%] Single-precision real
number
User User
+20
+21
S.OUT1 ML Output lower limit
value
-10 to 110 [%] Single-precision real
number
User User
+22
+23
S.PHPL/
S.IPD/S.BPI
RH Engineering value
upper limit
-999999 to 999999 Single-precision real
number
User User
+24
+25
S.PHPL/
S.IPD/S.BPI
RL Engineering value
lower limit
-999999 to 999999 Single-precision real
number
User User
+26
+27
S.PHPL PH Upper limit alarm
value
RL to RH
PL < PH
Single-precision real
number
User User
+28
+29
S.PHPL PL Lower limit alarm
value
RL to RH
PL < PH
Single-precision real
number
User User
+30
+31
S.PHPL HH Upper upper limit
alarm value
RL to RH
PH HH
Single-precision real
number
User User
+32
+33
S.PHPL LL Lower lower limit
alarm value
RL to RH
LL PL
S
ingle-precision real
number
User User
+38
+39
S.IN Filter coefficient 0 to 1 Single-precision real
number
User User
+40
+41
S.PHPL HS Upper/lower limit
alarm hysteresis
0 to 999999 [%] Single-precision real
number
User User
+42
+43
S.PHPL CTIM Variation rate
alarm check time
0 to 999999 [s] Single-precision real
number
User User
+44
+45
S.PHPL DPL Variation rate
alarm value
0 to 100 [%] Single-precision real
number
User User
+46
+47
S.IPD/S.BPI CT Control cycle 0 to 999999 [s] Single-precision real
number
User User
+48
+49
S.OUT1 DML Output variation
rate limit value
0 to 100 [%] Single-precision real
number
User User
+50
+51
S.IPD/S.BPI DVL Deviation limit
value
0 to 100 [%] Single-precision real
number
User User
+52
+53
S.IPD/S.BPI P Gain 0 to 999999 Single-precision real
number
User User
+54
+55
S.IPD/S.BPI/
S.OUT1
I
*1
Integral constant 0 to 999999 [s] Single-precision real
number
User User
+56
+57
S.IPD/S.BPI D/SDV Derivative
constant/DV
cumulative total
D: 0 to 999999 [s] Single-precision real
number
User
SDV:
-999999 to 999999 [%]
Single-precision real
number
System
+58
+59
S.IPD/S.BPI GW Gap width 0 to 100 [%] Single-precision real
number
User User
+60
+61
S.IPD/S.BPI GG Gap gain 0 to 999999 Single-precision real
number
User User