6 BASIC INSTRUCTIONS
6.7 Data Transfer Instructions
509
6
Transferring the same 16-bit binary data block (32 bits)
FMOVL(P)
These instructions transfer 16-bit binary data to the (n) points (1 to 4294967295) starting from the device specified.
Execution condition
Setting data
Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Applicable devices
Ladder ST
ENO:=FMOVL(EN,s,n,d);
ENO:=FMOVLP(EN,s,n,d);
FBD/LD
Instruction Execution condition
FMOVL
FMOVLP
Operand Description Range Data type Data type (label)
(s) Transfer target data or the device where the transfer target
data is stored
-32768 to 32767 16-bit signed binary ANY16
(d) Transfer destination start device 16-bit signed binary ANY16
*1
(n) Number of transfer data points 0 to 4294967295 32-bit unsigned binary ANY32
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s)  
(d) 
(n)  
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s) (d) (n)
EN ENO
sd
n