20 SERIAL COMMUNICATION INSTRUCTIONS
20.14 Reading User Frames
1717
20
20.14 Reading User Frames
G(P).GETE
These instructions read user frames.
Execution condition
Setting data
Description, range, data type
*1 When specifying setting data by using a label, define an array to secure enough operation area and specify an element of the array
label.
Ladder ST
ENO:=G_GETE(EN,U,s1,s2,d);
ENO:=GP_GETE(EN,U,s1,s2,d);
FBD/LD
Instruction Execution condition
G.GETE
GP.GETE
Operand Description Range Data type Data type (label)
(U) Start I/O number (first three digits in four-digit hexadecimal
representation) of a module
00H to FEH 16-bit unsigned binary ANY16
(s1) Start device where control data is stored Refer to the control data. Device name ANY16
*1
(s2) Start device for storing the registered data that has been
read.
Device name ANY16
*1
(d) Device that turns on for one scan upon completion of the
instruction
When the instruction completes with an error, (d)+1 also
turns on.
Bit ANYBIT_ARRAY
(Number of elements: 2)
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(U) (s1) (s2) (d)
EN ENO
dU
s1
s2