1078
7 APPLICATION INSTRUCTIONS
7.29 Logging Instructions
Resetting trigger logging
LOGTRGR
This instruction resets the trigger condition of the specified logging setting number.
Execution condition
Setting data
Description, range, data type
Applicable devices
Processing details
This instruction resets the LOGTRG instruction of the logging setting number specified by (s). The instruction disables the
LOGTRG instruction of the specified trigger logging setting number.
The LOGTRGR instruction turns off the special relays (logging completion, logging trigger, and after logging trigger) with
the logging setting number in the device specified by (s).
If the instruction is executed while buffer data is saved to an SD memory card, the execution of the instruction is made to
wait until all data is saved completely.
Operation error
Ladder ST
ENO:=LOGTRGR(EN,s);
FBD/LD
Instruction Execution condition
LOGTRGR
Operand Description Range Data type Data type (label)
(s) Logging setting number 1 to 10 16-bit signed binary ANY16
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K,
H
E $
(s) 
Error code
(SD0)
Description
3405H The value set to (s) is out of the range, 1 to 10.
RnCPU
RnENCPU
RnSFCPU RnSFCPURnPCPURnPCPU
(Standard) (Safety)
(Redundant)
(Process)
(s)
EN ENO
s