7 APPLICATION INSTRUCTIONS
7.7 Debugging and Failure Diagnostic Instructions
629
7
Generating a continuation error
PALERT(P)
This instruction generates a continuation error in the CPU module.
■Execution condition
■Description, range, data type
■Applicable devices
• This instruction generates a continuation error (error code: 1810H) in the CPU module. When the instruction is executed,
SM0 turns on and the ERROR LED of the CPU module turns on. SM1 does not turn on.
• Data (16-bit signed binary) specified by (s) is stored in the detailed information 2 of the error code 1810H.
• The PALERT(P) instruction is useful for debugging since a continuation error can be simulated at the start-
up of the system. The instruction execution point can be identified by checking the detailed information 2 of
the error code 1810H.
There is no operation error, except the error (error code: 1810H) which occurs by executing the PALERT(P) instruction.
Ladder ST
ENO:=PALERT(EN,s);
ENO:=PALERTP(EN,s);
FBD/LD
Instruction Execution condition
PALERT
PALERTP
Operand Description Range Data type Data type (label)
(s) Data to be stored in the detailed information 2 of the error
code 1810H or device number where the data is stored
-32768 to 32767 16-bit signed binary ANY16
EN Execution condition Bit BOOL
ENO Execution result Bit BOOL