11 PROCESS CONTROL INSTRUCTIONS
11.1 Overview
1185
11
Loop tag memory setting
The signs in the ladder diagram mean as follows.
Loop tag memory
(96 words)
Instruction used Item Standard value setting Data type
+0 16-bit unsigned binary
+1 MODE 8H 16-bit unsigned binary
+3 ALM 4000H 16-bit unsigned binary
+4 INH 4000H 16-bit unsigned binary
+10 S.PHPL PV 0.0 Single-precision real number
+12 S.OUT1 MV 0.0 Single-precision real number
+14 S.2PID SV 0.0 Single-precision real number
+16 S.2PID DV 0.0 Single-precision real number
+18 S.OUT1 MH 100.0 Single-precision real number
+20 S.OUT1 ML 0.0 Single-precision real number
+22 S.PHPL RH 100.0 Single-precision real number

+46 S.2PID CT 1.0 Single-precision real number
+48 S.OUT1 DML 100.0 Single-precision real number
+50 S.2PID DVL 100.0 Single-precision real number
+52 S.2PID P 1.0 Single-precision real number
+54 S.2PID I 10.0 Single-precision real number
+56 S.2PID D 0.0 Single-precision real number
+58 S.2PID GW 0.0 Single-precision real number
+60 S.2PID GG 1.0 Single-precision real number
+62 S.OUT1 MVP 0.0 Single-precision real number
+64 S.2PID 0.0 Single-precision real number
+66 S.2PID 1.0 Single-precision real number

+90 0.0 Single-precision real number
+92 0.0 Single-precision real number
+94 0.0 Single-precision real number
Item Instruction name
S.IN S.PHPL S.2PID S.OUT1
(1) Input data start device R0 R20 R40 R60
(2) Block memory start device R100 R120 R140 R160
(3) Operation constant start device R200 Null character string ("") R240 R260
(4) Loop tag memory start device R1000
(5) Set value start device R300
(2) (3) (4) (5)(1)