11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
Loop stop processing (5)
The following processing is performed according to the SPA status of the alarm detection (ALM).
Operation error
SPA status Processing details
1 Performs the following operations and terminates the S.IN instruction.
The last output value (BW) is held.
The control mode (MODE) is set to MAN.
All of the alarm bits (BB1, BB2, and BB3) are set to 0.
ALM SEA is set to 0.
0 Performs "range check (1)".
Error code
(SD0)
Description
3400H An invalid operation (such as division by zero) is performed.
3402H The value specified by (s1), (d1), (s2), or (d2) is a subnormal number or NaN (not a number).
3403H An overflow has occurred.
3405H Upper limit range error occurrence (HH) < upper limit range error return (H), lower limit range error return (L) < lower limit range error
occurrence (LL), or input upper limit (NMAX) < input lower limit (NMIN)