1206
11 PROCESS CONTROL INSTRUCTIONS
11.2 I/O Control Instructions
This instruction calculates the manipulated value (MV) from the input value (E1=MV) in the device specified by (s1), and
stores the result in the device specified by (d1). The instruction also performs variation rate & upper/lower limiter, reset
windup, and output conversion processing of the calculated manipulated value (MV).
The following is the processing block diagram of the S.OUT1 instruction. (The numbers (1) to (6) in the diagram indicate the
order of the processing.)
MODE
SPA
ERRI¸MLI
ERRI¸MHI
ERRI¸DMLI
MHA
MLA
DMLA
TRKF
BB2
BB3
BB1
AND
AND
OR
BB4
AND
BW
(6)
MAN
E1
(1) (2) (3) (4) (5)
(6)
Other than
MAN, CMB,
CMV, LCM
Mode
determination
MAN, CMB, CMV, LCM
Input addition
Variation rate,
upper/lower
limiter
Reset windup
Output
conversion
Loop stop
determination
RUN (SPA=0)
STOP (SPA=1)
Alarm clear
Upper limit alarm
Lower limit alarm
Variation rate alarm
OFF (all bits)
OFF (all bits)
Loop stop
processing
BW=Last value
MH, ML, DML
NMAX, NMIN
MV
MVP