1288
11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
Input data
Block memory
Operation constant
Local work memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
Processing details
This instruction sets the lag time (T
1
) of (s2) and the lead time (T
2
) and performs lead-lag compensation according to the
actuating signal (e1).
Operand: (s1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Input value -999999 to 999999 [%] Single-precision
real number
User
+2 e1 Actuating signal
0: Lead-lag compensation
1: No lead-lag compensation
16-bit unsigned
binary
User
Operand: (d1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 [%] Single-precision
real number
System
Operand: (s2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
T
1
Lag time 0 to 999999 [s] Single-precision
real number
1.0 User
+2
+3
T
2
Lead time 0 to 999999 [s] Single-precision
real number
1.0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1
n-1
Last input value Single-precision
real number
System
Lc: Lead-lag compensation
b15 b0
...
e1
t
t
t
1+T
2
S
1+T
1
S
E1
BW
BW
Lc
T
2
> T
1
T
2
< T
1