1288
11  PROCESS CONTROL INSTRUCTIONS
11.3  Control Operation Instructions
■Input data
■Block memory
■Operation constant
■Local work memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
■Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
This instruction sets the lag time (T
1
) of (s2) and the lead time (T
2
) and performs lead-lag compensation according to the 
actuating signal (e1).
Operand: (s1)
Position Symbol Name Recommended range Data type Standard 
value
Set by
+0
+1
E1 Input value -999999 to 999999 [%] Single-precision 
real number
 User
+2 e1 Actuating signal
0: Lead-lag compensation
1: No lead-lag compensation
16-bit unsigned 
binary
 User
Operand: (d1)
Position Symbol Name Recommended range Data type Standard 
value
Set by
+0
+1
BW Output value -999999 to 999999 [%] Single-precision 
real number
 System
Operand: (s2)
Position Symbol Name Recommended range Data type Standard 
value
Set by
+0
+1
T
1
Lag time 0 to 999999 [s] Single-precision 
real number
1.0 User
+2
+3
T
2
Lead time 0 to 999999 [s] Single-precision 
real number
1.0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard 
value
Set by
+0
+1
E1
n-1
Last input value  Single-precision 
real number
 System
Lc: Lead-lag compensation
t
t
t
1+T
2
S
1+T
1
S
E1
BW
BW
Lc
T
2 
> T
1
T
2 
< T
1