11 PROCESS CONTROL INSTRUCTIONS
11.3 Control Operation Instructions
1345
11
■Input data
■Block memory
■Operation constant
■Local work memory
The system uses this area as a work area.
To start the control from the initial status, clear data by using a sequence program.
■Execution cycle (T)
Set the execution cycle (T) in SD816 and SD817 in single-precision real number.
Operand (s1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
E1 Output set value -999999 to 999999 [%] Single-precision
real number
User
+2
+3
E2 Output control
value
-999999 to 999999 [%] Single-precision
real number
User
+4 e1 Mode switching
signal
0: Manual mode
1: Automatic mode
16-bit unsigned
binary
User
Operand (d1)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 [%] Single-precision
real number
System
Operand: (s2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
T Lag time 0 to 999999 [s] Single-precision
real number
1.0 User
+2
+3
a Lag band 0 to 999999 [%] Single-precision
real number
1.0 User
Operand: (d2)
Position Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
Xq Initial deviation
value
Single-precision
real number
1.0 System
+2
+3
Xp Deviation