11 PROCESS CONTROL INSTRUCTIONS
11.4 Correction Operation Instructions
1365
11
Block memory
Operation constant
Processing details
This instruction performs engineering value transformation of the input data (E1) and outputs it.
The S.ENG instruction performs the following operations.
Operation error
Operand: (d1)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
BW Output value -999999 to 999999 Single-precision
real number
System
Operand: (s2)
Device Symbol Name Recommended range Data type Standard
value
Set by
+0
+1
RH Engineering
value upper limit
-999999 to 999999 Single-precision
real number
100.0 User
+2
+3
RL Engineering
value lower limit
-999999 to 999999 Single-precision
real number
0.0 User
Error code Error content
3400H An invalid operation (such as division by zero) is performed.
3402H The value specified by (s1) or (s2) is a subnormal number or NaN (not a number).
3403H An overflow has occurred.
BW
t
4
3
0
-1
t
100
80
20
0
4
(RH)
-1
(RL)
ENG
E1
[%]
BW=
100
RH-RL
×E1+RL (E1=0 to 100%)