15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1457
15
+7 Number of resends Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
0 to 15 (times)
At completion of instruction
The number of resends performed (result) is stored.
0 to 15 (times)
0 to 15 User/
system
+8 Arrival monitoring time [CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
When "0" is specified in bit 8 of (s1)+0
•0: 10s
1 to 32767: 1 to 32767s
When "1" is specified in bit 8 of (s1)+0
•0: 10s
1 to 65535: 1 to 65535100ms
0 to 65535 User
[Ethernet]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
When "0" is specified in bit 8 of (s1)+0
Specify the TCP resend timer value or greater for the monitoring time till completion
of processing.
0 to (TCP resend timer value): The TCP resend timer value is assumed as the
monitoring time.
(TCP resend timer value + 1) to 16383: (TCP resend timer value + 1) to 16383s
When "1" is specified in bit 8 of (s1)+0
•0: 10s
1 to 65535: 1 to 65535100ms
0 to 65535 User
+9 Read data length Specify the number of words to be read.
When reading data from RCPU, QCPU, or LCPU
Channels 1 to 8 are used: 1 to 960 (words)
Channels 9 and 10 are used: 1 to 8192 (words)
When reading data from QnACPU
1 to 480 (words)
1 to 8192 User
+10 Not used 
+11 Clock setting flag The validity status (valid or invalid) of the data in (s1)+12 and later is stored. Note
that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
0: Invalid
1: Valid
System
+12 Clock data
(Set only in an
abnormal state)
Upper 8 bits: Month (01H to 12H)
Lower 8bits: Year (00H to 99H: Upper two digits of the year)
System
+13 Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
System
+14 Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
System
+15 Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
System
+16 Error detection network
number
When "0" is specified in bit 15 of (s1)+0
The network number of the station in which an error was detected is stored. (No
information is stored if an error is detected in the own station.)
1 to 239 (Network number)
When "1" is specified in bit 15 of (s1)+0 (Ethernet only)
The IP address (third and fourth octets) of the station where an error was detected is
stored.
b8 to b15: 3rd octet
b0 to b7: 4th octet
System
Operand: (s1)
Device Item Description Setting range Set by
b15 b7b8
……
b0