15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
1481
15
+8 Arrival monitoring time [CC-Link IE Controller Network or CC-Link IE Field Network]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
When "0" is specified in bit 8 of (s1)+0
•0: 10s
1 to 32767: 1 to 32767s
When "1" is specified in bit 8 of (s1)+0
•0: 10s
1 to 65535: 1 to 65535100ms
0 to 65535 User
[Ethernet]
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
When "0" is specified in bit 8 of (s1)+0
Specify the TCP resend timer value or greater for the monitoring time till completion
of processing.
0 to (TCP resend timer value): The TCP resend timer value is assumed as the
monitoring time.
(TCP resend timer value + 1) to 16383: (TCP resend timer value + 1) to 16383s
When "1" is specified in bit 8 of (s1)+0
•0: 10s
1 to 65535: 1 to 65535100ms
0 to 65535 User
+9 Write data length Specify the number of words to be written.
Writing to RCPU, QCPU, or LCPU
Channels 1 to 8 are used: 1 to 960 (words)
Channels 9 and 10 are used: 1 to 8192 (words)
Writing to QnACPU
1 to 480 (words)
1 to 8192 User
+10 Not used 
+11 Clock setting flag The validity status (valid or invalid) of the data in (s1)+12 and later is stored. Note
that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
0: Invalid
1: Valid
System
+12 Clock data
(Set only in an
abnormal state)
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Lower 2 digits of year (00H to 99H)
System
+13 Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
System
+14 Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
System
+15 Upper 8 bits: Year (00H to 99H: Upper two digits of the year)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
System
+16 Error detection network
number
The network number of the station in which an error was detected is stored. (No
information is stored if an error is detected in the own station.)
1 to 239 (Network number)
1 to 239 System
+17 Error-detected station
number
The station number of the station where an error was detected is stored. (No
information is stored if an error is detected in the own station.)
[Ethernet or CC-Link IE Controller Network]
1 to 120: Station number
[CC-Link IE Field Network]
125: Master station
1 to 120: Local station, intelligent device station, submaster station
1 to 120,
125
System
Operand: (s1)
Device Item Description Setting range Set by

Table of Contents