1500
15 NETWORK COMMON INSTRUCTIONS
15.1 Link Dedicated Instructions
The following figure shows the execution timing of the RECVS instruction.
The RECVS instruction is used in interrupt programs and processing is completed in a single scan.
When the RECVS instruction is used to read receive data from the same channel, the RECV instruction (for use in the main
program) cannot be used in combination.
Operation error
When completed successfully
When completed with an error
Error code
((s)+1)
Description
C000H to CFFFH MELSEC iQ-R Ethernet User's Manual (Application)
D000H to DFFFH MELSEC iQ-R CC-Link IE Field Network User's Manual (Application)
E000H to EFFFH MELSEC iQ-R CC-Link IE Controller Network User's Manual (Application)
SEND
OFF
END0END0END0END0END0
OFF OFF
OFF
ON
ON
OFF
END ENDEND
IRET
0END0END0
RECVS
1 scan
(With arrival confirmation)
Channel n
Data
transmission
Storage
notification
Channel n
Sequence scan
Start contact
CPU module on
the sending
station
Completion device
(d)
Completion status
indication device
(d)+1
Network
module
Network
module
CPU module on
the own station
Interrupt program
Sequence scan
Device for storing
the receive data (d1)
Receive data
1 scan
END ENDEND
IRET
0END0END0
RECVS
Channel n
Network
module
CPU module on
the own station
Interrupt program
Sequence scan
Completion status
(s)+1
Error code