22 POSITIONING INSTRUCTIONS
22.3 Teaching
The following figure shows the operation at completion of the TEACH instruction.
Precautions
For a single axis, any of the following instructions cannot be executed concurrently with a G.ABRST instruction. although
different axes, any of the following can be executed concurrently with a GP.TEACH instruction.
The TEACH instruction is executed when the BUSY signal [XC, XD, XE, or XF] is off. While the BUSY signal [XC, XD,
XE, XF] is on, the instruction cannot be executed. (No processing is performed.) Before executing the instruction, check
that the BUSY signal [XC, XD, XE, XF] of the corresponding axis is off.
Operation error
Positioning start instruction (PSTRT)
Absolute position restoration instruction (ABRST)
Teaching instruction (TEACH)
Error code
((s)+1)
Description
1863H A value other than 0 or 1 was set in "Teaching data selection" of (s)+2.
1864H A value other than 1 to 600 was set in "Positioning data number" of (s)+3
1865H An instruction was specified for an undefined axis (e.g. the GP.TEACH3 instruction was specified when RD75P2 is used).
END0END0END0END0END0
OFF
OFF
OFF
OFF
ON
ON
Sequence scan
TEACH instruction
Completion device (d)
Completion status
indication device (d)+1
Completed with an error
Execution of
the instruction
Completed
successfully
1 scan
Completion of the instruction