APPX
Appendix 1 Instruction Processing Time
2027
A
S.SPI Set value pattern = 3 (without a cascade)
Tracking bit = 0
Operating time = Sample cycle (ST=STHT)
Integral constant 0
The loop is running in AUT mode and the ALM bit does not turn on.
35.900 36.900
S.IPD Set value pattern = 3 (without a cascade)
Tracking bit = 0
Execution cycle = Control cycle = 1
Integral constant 0
Derivative constant 0
The loop is running in AUT mode and the ALM bit does not turn on.
45.600 47.800
S.BPI Set value pattern = 3 (without a cascade)
Tracking bit = 0
Execution cycle = Control cycle = 1
Integral constant 0
The loop is running in AUT mode and the ALM bit does not turn on.
34.700 35.400
S.R Set value pattern = 3 (without a cascade)
Tracking bit = 0
Execution cycle = Control cycle = 1
The loop is running in AUT mode.
31.300 32.600
S.PHPL The loop is running in AUT mode and the ALM bit does not turn on. 38.000 39.500
S.LLAG Input data = 50 with lead-lag compensation
Lead time = 1, Lag time = 1
21.100 21.400
S.I Input data = 50, Integral time = 1
Output initial value = 0
17.100 17.700
S.D Input data = 50, Derivative time = 1
Output initial value = 0
18.500 18.900
S.DED Input data = 50
Operation control signal 0 1
Data sampling interval = 1
Sampling count = 10
Output initial value = 0
Initial output switching = 0
10.200 10.900
S.HS Number of inputs = 5
Input data = 50, 100, 150, 200, 250
13.300 13.700
S.LS Number of inputs = 5
Input data = 50, 100, 150, 200, 250
13.000 13.200
S.MID Number of inputs = 5
Input data = 50, 100, 150, 200, 250
17.400 17.900
S.AVE Number of inputs = 2, Input data = 50, 100 16.000 16.300
S.LIMT Input data = 50
Upper limit value = 100
Lower limit value = 0
Upper limit hysteresis = 0
Lower limit hysteresis = 0
18.200 18.700
S.VLMT1 Input data = 50
Positive direction limit value = 100
Negative direction limit value = 100
Positive direction hysteresis = 0
Negative direction hysteresis = 0
17.500 17.600
S.VLMT2 Input data = 50
Positive direction limit value = 100
Negative direction limit value = 100
Positive direction hysteresis = 0
Negative direction hysteresis = 0
17.300 17.800
S.ONF2 Input data = 10
Set value pattern = 3 (without a cascade)
Tracking bit = 0
Execution cycle = Control cycle = 1
The loop is running in MAN mode.
32.600 34.100
Instruction name Condition Processing time (s)
Minimum Maximum