6 BASIC INSTRUCTIONS
6.6 Data Conversion Instructions
387
6
Processing details
These instructions convert the single-precision real number in the device specified by (s) to 16-bit signed binary data, and
store the converted data in the device specified by (d).
After conversion, the first digit after the decimal point of the single-precision real number is rounded off.
When an input value is set using the engineering tool, a rounding error may occur. For the precautions on setting an input
value using the engineering tool, refer to the following.
Page 49 Precautions
The following program example converts, when M0 turns on, the single-precision real number stored in D0 and D1 to 16-bit
signed binary data, and stores the converted data in D100.
Operation error
Error code
(SD0)
Description
3401H The single-precision real number in the device specified by (s) is out of the range, -32768 to 32767.
3402H An unusual number is set to (s).
The single-precision real number set to (s) is not within the following range:
0, 2
-126
|(s)|<2
128
The value set to a device or label is -0, a subnormal number, NaN (not a number), or .
SM402
(s) (d)
M0
(d)
(-1235)
FB2DH
b15 b0
D100
(s)
b31 b16
(-1234.5)
5000H
C49AH
b15 b0
D1, D0
 
EMOVP E-1234.5 D0
FLT2INT D0 D100