7 APPLICATION INSTRUCTIONS
7.6 Reading/Writing Data Instructions
625
7
The following figure shows how data is added.
[Specify the file to which data will be written.] (Even if the file exists, it is deleted and re-created.)
[Added to the end of the file]
Execution/completion type: Writing data after converted to CSV format (Decimal (signed 16-bit data))
Number of columns specification: 4H
Data type specification: Words
File position: 00000000H (from the beginning of the file)
Write start device: D0
Number of request write data: 6H
(1) Starting row
(2) Data in the device (write data)
N: Number of data
Execution/completion type: Writing data after converted to CSV format (Decimal (signed 16-bit data))
Number of columns specification: 3H
Data type specification: Words
File position: FFFFFFFFH (added to the end of the file)
Write start device: D7
Number of request write data: 8H
(1) Starting position
(2) Data in the device (write data)
N: Number of data
1, 2, 3, 4CRLF
5, 6CRLF
K6
K1
K2
K3
K4
K5
K6
K5
K7
K8
K9
K10
K11
K12
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
D10
D11
D12
D13
(1)
(2)
N
Row 1
Column 1
Column 2 Column 3 Column 4
Row 2
1,2,3,4CRLF
5,6CRLF
K6
K1
K2
K3
K4
K5
K6
K8
K7
K8
K9
K10
K11
K12
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
D10
D11
D12
D13
7,8,9CR LF
10 , 11 , 12 CR LF
13 , 14 CR LF
K13 D14
K14 D15
(2)
N
(1)
Row 1
Row 2
Row 3
Row 4
Row 5
Column 1 Column 2 Column 3 Column 4