7 APPLICATION INSTRUCTIONS
7.12 Data Control Instructions
Applicable devices
Processing details
These instructions control the output value to be stored in the device specified by (d) by checking the input value (16-bit
binary data) in the device specified by (s3) with the upper and lower limit values specified by (s1) and (s2). The output value
is controlled as follows.
To control the input value only with the upper limit, set the minimum value within the setting range in (s1).
To control the input value only with the lower limit, set the maximum value within the setting range in (s2).
Operation error
Operand Bit Word Double word Indirect
specification
Constant Others
X, Y, M, L,
SM, F, B, SB,
FX, FY
J\ T, ST, C, D, W,
SD, SW, FD, R,
ZR, RD
U\G, J\,
U3E\(H)G
Z LT, LST,
LC
LZ K, H E $
(s1) 
(s2) 
(s3) 
(d)  
Condition Output value
Lower limit value (s1) > Input value (s3) Lower limit value (s1)
Upper limit value (s2) < Input value (s3) Upper limit value (s2)
Lower limit value (s1) Input value (s3) Upper limit value (s2) Input value (s3)
Error code
(SD0)
Description
3405H The lower limit value specified by (s1) is greater than the upper limit value specified by (s2).
0
(d)
(s3)
(s1)
(s2)