282 TimeProvider 2300/2700 User’s Guide 098-00564-000 Revision A3 – July, 2013
Appendix A System Messages
System Notification Messages
GNSS signal low 093 Minor No GNSS signal low
GNSS signal normal
Check Antenna
installation
Check if Antenna
cable is connected
properly.
Installation should
conform to the
guidelines as
described in
Appendix C.
No action required
GNSS antenna
voltage out of range
(#)
094 Major No GNSS antenna voltage
out of range (#)
GNSS antenna voltage
out of range cleared
Check for short circuit in
the antenna cable.
No action required
GNSS antenna
current out of range
(#)
095 Major No GNSS antenna current
out of range (#)
GNSS antenna current
out of range cleared
Not supported at this
time.
No action required
GNSS antenna
short-circuit
096 Minor No GNSS antenna
short-circuit
GNSS antenna
short-circuit cleared
Check for short circuit in
the antenna cable.
No action required
GNSS antenna
open-circuit
097 Minor No GNSS antenna
open-circuit
GNSS antenna
open-circuit cleared
Check for Antenna not
connected or AC coupled
splitter. If using a splitter
you must at least draw
10mA of current from the
TP2700. This can be
achieved by adding a 50
ohm termination.
No action required
Table A-1. System Notification Messages (Continued)
Description
Event
ID
Msg
Level
Trans-
itory
MsgText Corrective Action

Table of Contents