And it is cancelled after a setting time by data parameter DT013; M32 is to execute
lubricating output
and the output is cancelled after a time set by DT013. If the setting time is not yet up, M33
is executed
to cancel the lubricating output.
2. Automatic lubricating (DT017>0)
For automatic lubricating, the system executes the lubricating in the time set by DT017
and the
stops the output. After lubricating interval time set by DT016, the output is done again, it
does
repetitively like this. During the automatic lubricating, M32, M33 codes as well as the key
are
all active.
Parameter setting:
PLC parameter: K10.1 1/0: the spindle lubricating/cooling output remains/closes in reset;
PLC parameter:K16.2 1/0: whether the lubricating outputs in power-on when the
automatic
lubricating is valid;
PLC data DT005: M execution duration(ms);
PLC data DT013: lubricating start time (0-60000ms)(0:lubricating time is not limited);
PLC data: DT016 automatic lubricating interval time (ms);
PLC data: DT017: automatic lubricating output time (ms).
3.2.5 Chuck control
: press it to switch the chuck releasing/clamping in any mode.
Function description:
When the chuck control is invalid, the system alarms in executing the chuck control M
command;
When the system checks the chuck clamping (K12.1=1), the spindle cannot be started
when the
chuck is not clamped, and the chuck cannot be released after the spindle is started;
When using the input signal controls the chuck operation, the spindle should stop and
delay the
time set by DT21, the control is valid.
Chapter 3 Manual Operation
213
Operation
Parameter setting:
PLC parameter: K12.0 1/0: chuck control valid/invalid;
PLC parameter: K12.1 1/0: do not check/check the chuck clamping before the spindle
start;
PLC parameter: K12.2 1/0: chuck outer/inner control mode;
PLC parameter: K12.3 1/0: check/not chuck in-position signal;
PLC data: DT018: chuck pulse output width(ms);