EasyManua.ls Logo

TOMATECH TAC-100XT - Page 304

TOMATECH TAC-100XT
415 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TOMATECH AUTOMATION
Signal
type Sign Signal
interface Address Function
CLPY CN62.31 Y2.2 Yellow— normal state (non-running,
non-alarm state)
CLPG CN62.32 Y2.3 Green—running state
Output
signal
CLPR CN62.33 Y2.4 Red—alarm state
2.8.23 Extended M Function
� Relevant signals(standard PLC program)
366
Ⅲ Connection
Signal interface Address Address characters Function
CN62.36 Y2.7 EMOT1 Extended M function signal 1
CN62.40 Y3.3 EMOT2 Extended M function signal 2
� Relevant commands
M34 Extended M function signal 1(EMOT1)outputs
M35 Extended M function signal 1(EMOT1)closes output
M36 Extended M function signal 2(EMOT2)outputs
M37 Extended M function signal 2(EMOT2)closes output
� Control parameters
PLC parameters
K 1 8 EXTM RSTM
EXTM =0:extended M function is invalid.
=1:extended M function is valid.
RSTM =0:extended M function closes output when emergency stop, reset.
=1:extended M function remains output when emergency stop, reset.
Note: Extended M function is invalid when the multi-spindle function is valid because of address
multiplexing.
� Function explanation
1. When M34 is executed, extended M function 1 (EMOT1) outputs; when M35 is done, its
output is
closed.
2. When M36 is executed, extended M function 2 (EMOT2) outputs; when M37 is done, its
output is
closed.
3. Whether extended M function output is closed is set by K18.6 when emergency stop,
reset.
2.8.24 HOLD Control
� Relevant signals(standard PLC program)
Signal
interface

Table of Contents