TOMATECH AUTOMATION
Signal
type Sign Signal
interface Address Function
CLPY CN62.31 Y2.2 Yellow normal state (non-running,
non-alarm state)
CLPG CN62.32 Y2.3 Greenrunning state
Output
signal
CLPR CN62.33 Y2.4 Redalarm state
2.8.23 Extended M Function
Relevant signalsstandard PLC program
366
Connection
Signal interface Address Address characters Function
CN62.36 Y2.7 EMOT1 Extended M function signal 1
CN62.40 Y3.3 EMOT2 Extended M function signal 2
Relevant commands
M34 Extended M function signal 1EMOT1outputs
M35 Extended M function signal 1EMOT1closes output
M36 Extended M function signal 2EMOT2outputs
M37 Extended M function signal 2EMOT2closes output
Control parameters
PLC parameters
K 1 8 EXTM RSTM
EXTM =0extended M function is invalid.
=1extended M function is valid.
RSTM =0extended M function closes output when emergency stop, reset.
=1extended M function remains output when emergency stop, reset.
Note: Extended M function is invalid when the multi-spindle function is valid because of address
multiplexing.
Function explanation
1. When M34 is executed, extended M function 1 (EMOT1) outputs; when M35 is done, its
output is
closed.
2. When M36 is executed, extended M function 2 (EMOT2) outputs; when M37 is done, its
output is
closed.
3. Whether extended M function output is closed is set by K18.6 when emergency stop,
reset.