172 Upgrade and Maintenance Manual RX1330 M3
Hard disk drive (HDD) / solid state drive (SSD)
7.3.3.2 Removing a 3.5-inch HDD module
Ê Pinch the green locking clips and open the locking lever (see figure 90).
Ê Pull the HDD module out a few centimeters.
Ê Wait about 30 seconds to allow the HDD to spin down.
I This period is necessary for the RAID controller to recognize that an
HDD module has been removed and for the HDD to come to a stop.
Ê Pull the HDD module completely out of its bay.
7.3.3.3 Installing a 3.5-inch dummy module
V CAUTION!
If the removed HDD module is not replaced immediately, always replace
a dummy module into the unused HDD bay to comply with applicable
EMC regulations and satisfy cooling requirements.
Figure 92: Installing the 3.5-inch dummy module
Ê Push the dummy module into the empty bay until it engages.
7.3.3.4 Concluding steps
No steps needed.