190 Upgrade and Maintenance Manual
RX200 S8
Expansion cards and backup units
9.5.5.5 Concluding steps
Ê "Installing the riser module 3" on page 61
Ê "Reassembling" on page 52
Ê "Connecting the server to the mains" on page 57
Ê "Switching on the server" on page 58
9.5.6 Replacing a BBU
V CAUTION!
Dispose of used battery properly. Keep away from children.
Do not throw battery backup units into the trash can. Batteries must
be disposed of in accordance with local regulations concerning
special waste.
9.5.6.1 Preliminary steps
Ê "Disabling SVOM boot watchdog functionality" on page 64
Ê "Shutting down the server" on page 46
Ê "Disconnecting the server from the mains" on page 47
Ê "Getting access to the component" on page 47
Ê "Removing the riser module 3" on page 60
9.5.6.2 Removing the defective BBU
Ê Remove the BBU with the holder as described in section "Removing the
BBU with the holder" on page 184.
Ê Remove the BBU from the holder as described in section "Removing the
BBU from the holder" on page 186.
Upgrade and Repair Unit
(URU)
Hardware: 15 minutes
Tools: tool-less