5.2 Configuration
5.2.1 Parameters
Parameter Description
Choices
ContactInput Mark a specific contact input as Used or Unused. Used, Unused
SignalInvert Inversion makes signal true if contact is open Normal, Invert
SeqOfEvents Record contact transitions in sequence of events Enable, Disable
DiagVoteEnab Enable voting disagreement diagnostic Enable, Disable
Signal Filter Contact input filter in milliseconds Zero, Ten, Twenty, Fifty, Hundred
5.2.2 Inputs
Input Direction Type
Contact01 Input BOOL
↓ ↓ ↓
Contact24 Input BOOL
5.2.3 Variables
Note The following variable names are displayed differently depending on redundancy of I/O pack (R, S, or T).
Variable Description Direction Type
L3DIAG_YDIA_x I/O diagnostic indication, where x is R, S, or T
Input
BOOL
LINK_OK_YDIA_x I/O link okay indication, where x is R, S, or T BOOL
ATTN_YDIA_x I/O attention indication, where x is R, S, or T BOOL
IOPackTmpr_x I/O pack temperature, where x is R, S, or T REAL
PS18V_YDIA_x I/O 18 V power supply indication, where x is R, S, or
T
BOOL
PS28V_YDIA_x I/O 28 V power supply indication, where x is R, S, or
T
BOOL
YDIA Discrete Input Modules GEH-6855_Vol_II System Guide 119