280
Description Platform hardware does not match configuration
Possible Cause
During commissioning/maintenance: Platform type identified in the application configuration does not match actual
hardware
During normal operation: Hardware failure
Solution
Fix the platform type in the ToolboxST application. From the General tab, select General Properties and Platform.
Rebuild and download the application.
If problem persists, replace the controller.
282
Description Firmware Load Error - application independent processes failed to initialize
Possible Cause Runtime malfunction. An application-independent firmware process could not be started successfully.
Solution
Reload firmware and application and restart.
If controller is a UCSA, try formatting and reloading the flash memory.
If I/O pack has diagnostic: try to re-download the base load.
Replace the controller or I/O module.
283
Description Firmware error - Internal process crashed
Possible Cause Runtime or hardware malfunction (runtime process failed).
Solution
Reload firmware and application and restart.
If controller is a UCSA, try formatting and reloading the flash memory.
If this does not work, replace the controller.