Description JPDM-[ ] fuse FU4 (J1 connector) is blown
Possible Cause
The specified fuse is blown.
The 28 V R power supply input is not connected.
Solution
Replace the fuse.
Verify the power supply connections to the terminal board.
69, 72
Description JPDM-[ ] fuse FU5 (J1 connector) is blown
Possible Cause
The specified fuse is blown.
The 28 V R power supply input is not connected.
Solution
Replace the fuse.
Verify the power supply connections to the terminal board.
70, 73
Description JPDM-[ ] fuse FU6 (J1 connector) is blown
Possible Cause
The specified fuse is blown.
The 28 V R power supply input is not connected.
Solution
Replace the fuse.
Verify the power supply connections to the terminal board.
PDM Power Distribution Modules GEH-6855_Vol_II System Guide 327