GE Mark VIeS - JPDC-DC 125 V Gnd Fdbk Mag (JD1;JZ2 Connector) out of Range; JPDC-Fuse FU71 or FU72 (J7 A Connector) Is Blown or SW7 A Switched off

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
173
Description JPDC-DC 125V Gnd fdbk mag (JD1/JZ2 connector) out of range.
Possible Cause
The dc 125 ground feedback magnitude is greater than Gnd_Mag_Trig_Volt.
Gnd_Mag_Trig_Volt is set too low.
One side of the DC 125 V source voltage is grounded.
Solution
Verify that Gnd_Mag_Trig_Volt is set correctly.
Check the connections to the specified connector.
Verify the grounding of the dc input signals. Refer to the JPDC help documentation.
If DC 125V input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
174
Description JPDC-Fuse FU71 or FU72 (J7A connector) is blown or SW7A switched OFF.
Possible Cause
The specified switch is turned off and FuseDiag is enabled.
The specified fuse is blown.
The 125 V dc input is not connected.
Solution
If the switch is turned off (output is not used), disable the diagnostic by setting FuseDiag to Disable.
If the output is used, verify that the switch is turned on.
Replace the fuse.
Verify the 125 V dc input connections to the terminal board.
If the 125 V dc input is not used, this diagnostic alarm can be disabled by setting the InputDiagEnab parameter on the
associated input (DC_125VFdbkMag) to Disabled.
346 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II