2408
Description EtherCAT ENI file does not match bus configuration
Possible Cause ENI File imported in ToolboxST does not match the discovered network.
Solution
Verify ENI file matches the network connected to the Mark VIe controller.
Verify EtherCAT network is connected and intact.
2409
Description EtherCAT redundant Ethernet links crossed
Possible Cause Main and Redundant Ethernet links are swapped on the controller.
Solution Switch the EtherCAT Network connections on the controller.
2410
Description EtherCAT configuration is not supported
Possible Cause
The ENI file contains unsupported commands or features
The ENI file contains commands that are unsupported in redundancy
Solution
Remove unsupported commands or disable unsupported features.
In redundant operation, replace LRW commands with LRD / LWR.
Controllers GEH-6855_Vol_II System Guide 83