101
Description I/O pack internal reference voltage out of limits
Possible Cause The calibration reference voltage for the analog inputs is more than ±5% from the expected value,
indicating a hardware failure.
Solution
• Check the I/O pack ground quality through mounting bolts.
• Cycle power to the I/O pack.
• Replace the I/O pack.
102
Description I/O pack internal null voltage out of limits
Possible Cause The calibration Null voltage for the analog inputs is more than ±5% from the expected value, indicating a
hardware failure.
Solution
• Check the I/O pack ground quality through mounting bolts.
• Cycle power to the I/O pack.
• Replace the I/O pack.
128
Description Logic Signal [ ] Voting Mismatch
Possible Cause N/A
Solution N/A
224-235
Description Input Signal [ ] Voting Mismatch, Local=[ ], Voted=[ ]
Possible Cause
• Voter disagreement between the R, S and T I/O packs
• I/O pack is not seated correctly on the terminal board.
Solution
• Adjust the parameter TMR_DiffLimt or correct the cause of the difference.
• Re-seat the I/O pack to the terminal board.
• Replace the I/O pack.