Description CDH EGD fault detected by the R processor
Possible Cause
CDH EGD producer is powered down
Producer is unhealthy
Ethernet connection(s) failure
Solution
Ensure all EGD producers are powered up and healthy.
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
Replace the producer processor module.
494
Description CDH EGD fault detected by the S processor
Possible Cause
CDH EGD producer is powered down
Producer is unhealthy
Ethernet connection(s) failure
Solution
Ensure all EGD producers are powered up and healthy.
Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
Replace the producer processor module.