292
Description Application Error - application overrunning the frame
Possible Cause Application cannot start within frame.
Solution Check application loading and reduce the amount of application code or frequency of execution. Build
application and download to all controllers.
294
Description Controller CPU overtemperature, Temp [ ] °C, Threshold [ ] °C
Possible Cause
Excessive ambient temperature
Hardware malfunction
Fan loss
Solution
Check the fan (if applicable), the ambient temperature, and for the presence of dust.
Replace the controller.
300
Description Application Code Load Failure
Possible Cause
During commissioning/maintenance:
Invalid application configuration
During normal operation:
Firmware or hardware malfunction
Solution
Rebuild and download the application to all controllers.
Reload firmware and application.
If problem persists, replace the controller.