Current Inputs
CurrentInputs
Low_Input Low_Value High_Input High_Value InputFilter ExternPwrEnab Min_MA_
Input
Max_MA_Input
Descriptions Input mA at
Low Value
Low Input in
Engineering
Units
Input MA at
High Value
High Input in
Engineering
Units
Filter
Bandwidth in
Hz
Enable External
Power for 4-20ma
inputs
Set the minimum
mA for healthy
input
Set the maximum mA
for healthy input
Choices {defaults} {4} {0} {20} {100} 0.75hz
1.5hz
12hz
3hz
6hz
{Unused}
Disable {Enable} {3} {22.5}
Low_Input, Low_Value, High_Input, High_Value settings are used by the YUAA firmware to define the linear relationship between mA and customer-defined engineering
units. The I/O Point value will be in Engineering units. Engineering units are specific to the field device being used.
Current Inputs (continued)
Hart_Enable
Hart_CtrVars Hart_ExStatus Hart_MfgID
Hart_DevType Hart_DevID
Enable Hart protocol on
this channel
Number of control vars to
read from Hart device
Set to zero if not used.
Number of extended status
bytes to read from Hart
device
Set to zero if not used.
Hart Field Device -
Manufacture ID
Note: For HART7 field
devices, this is the upper
byte of Expanded Device
Type
A diagnostic alarm is sent
if the field device ID differs
from this value and the
value is non-zero. This
value can be uploaded
from the YUAA if the field
device is connected.
(Right-click on device
name and select Update
HART IDS)
Hart Field Device - Device
Type
Note: For HART7 field
devices, this is lower byte
of Expanded Device Type
Hart Field Device - Device
ID
{Enable}
Disable
{0}
0-5
{0}
0-26
{0}
0-255
{0}
0-255
{0}
0-116777215
202 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II