Description CDH EGD fault detected by the T processor
Possible Cause
• CDH EGD producer is powered down
• Producer is unhealthy
• Ethernet connection(s) failure
Solution
• Ensure all EGD producers are powered up and healthy.
• Check for a defective Ethernet cable from producer to network switch. Replace the cable(s).
• Check for a defective network switch by placing the producer's Ethernet cable into an empty port. If the problem persists,
replace the network switch.
• Replace the producer processor module.
496
Description Failed to incorporate the user-configured frame state timeouts
Possible Cause
• Invalid user-configured frame state timeout values
• Failed to parse the user-configured frame state timeouts file
Solution
• Timeout values configured by the user must satisfy the condition
Frame Rate > Output Timeout > App Timeout > Input Timeout > 0.
• Rebuild the application and force an offline download of the application to the controller.
497-498
Description Fan loss detected for controller fan [ ]
Possible Cause
• Hardware malfunction
• Fan power not applied
Solution
• Check the fan.
• Verify that the power connector is properly inserted.
• Replace the fan.
64 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II