Description I/O pack in stand alone mode
Possible Cause
During commissioning or maintenance:
The I/O pack or module configuration is invalid.
During normal operation:
The hardware failed.
Solution
During commissioning or maintenance:
Rebuild the system, then download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
5
Description I/O pack in remote I/O mode
Possible Cause
During commissioning or maintenance:
The I/O pack or module configuration is invalid.
During normal operation:
The hardware failed.
Solution
During commissioning or maintenance:
Rebuild the system, then download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
6
Description Special User Mode active. Now: [ ]
Possible Cause
During commissioning or maintenance:
The I/O pack or module configuration is invalid.
During normal operation:
The hardware failed.
Solution
During commissioning or maintenance:
Rebuild system, then download the application and the configuration to the I/O pack or module.
During normal operation:
Replace the I/O pack or module.
444 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II