185
Description JPDC-P28v-S volt fdbk (JS/PS connector) out of range.
Possible Cause
The 28 V power supply input is out of range. It should be within ±5% of 28 V.
The 28 V power supply has not been connected.
There may be a power supply problem.
Solution
The input is not used. Set PS28vEnable to Disable.
Verify the power supply connections (specified connector) to the terminal board.
Verify that the power supply feedback on the JPDC Inputs tab in the ToolboxST configuration is within the expected
tolerance (±5%).
186
Description JPDC-P28v-T volt fdbk (JT/PT connector) out of range.
Possible Cause
The 28 V power supply input is out of range. It should be within ±5% of 28 V.
The 28 V power supply has not been connected.
There may be a power supply problem.
Solution
The input is not used. Set PS28vEnable to Disable.
Verify the power supply connections (specified connector) to the terminal board.
Verify that the power supply feedback on the JPDC Inputs tab in the ToolboxST configuration is within the expected
tolerance (±5%).