69
Description Channels 1, 5, 9, 13 ADC Failure. Status [ ]
Possible Cause The I/O pack failed.
Solution Replace the I/O pack.
70
Description Channels 2,6,10 ADC Failure. Status [ ]
Possible Cause The I/O pack failed.
Solution Replace the I/O pack.
71
Description Channels 3,7,11 ADC Failure. Status [ ]
Possible Cause The I/O pack failed.
Solution Replace the I/O pack.
72
Description Channels 4,8,12 ADC Failure. Status [ ]
Possible Cause The I/O pack failed.
Solution Replace the I/O pack.
73
Description 1x2x Phase Calibration Level [ ] Failure on Channel [ ]
Possible Cause The I/O pack failed to auto-calibrate when powered on.
Solution Replace the I/O pack.
74
Description Current Operating Mode is incompatible with this hardware
Possible Cause The selected Operating Mode is not supported by this module. This is likely caused by installing a
replacement module without updating ToolboxST. This alarm may be accompanied by Voter Disagreement diagnostics.
Solution
Change the Operating Mode parameter to Legacy.
Replace this module with a functionally compatible module.
274 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II