268
Description Firmware Load Error - Incompatible FPGA Revision: Found [ ] Need [ ]
Possible Cause
During commissioning or maintenance:
• Incompatible version of firmware downloaded
During normal operation:
• There is a hardware failure.
Solution
During commissioning or maintenance:
• Confirm the correct installation of the ToolboxST application.
During normal operation:
• Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
• Rebuild the application and download the firmware and the application code to the affected I/O pack or module.
• Replace the I/O pack or module.
269
Note This alarm is obsolete.
Description EGD communication Initialization Failure
Possible Cause Internal runtime error
Solution
• Restart the I/O pack or module.
• Upgrade the I/O pack or module firmware and application code.
• If the problem persists, replace the I/O pack or module.
270
Note This alarm is obsolete.
Description EGD communication terminated
Possible Cause Internal runtime error
Solution
• Restart the I/O pack or module.
• Upgrade the I/O pack or module firmware and application code.
• If the problem persists, replace the I/O pack or module.
456 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information