8.3.4 Component Editor
8.3.4.1 Parameters
Parameter Description
Choices
SystemLimits Allows user to temporarily disable all system limit checks for testing purposes.
Setting this parameter to Disable will cause a diagnostic alarm to occur.
Enable (default)
Disable
OperatingMode Enhanced enables enhanced algorithms for YVIBS1B that are not compatible
with YVIBH1A, including Low Latency Peak-Peak Algorithm and Vibration
RMS Algorithm
Legacy (default)
Enhanced
Vib_PP_Fltr First order filter time constant (sec) cannot be disabled 0.01 to 2
(default is 0.10)
MaxVolt_Prox Maximum Input Volts (pk-neg), healthy Input, Prox -4 to 0
(default is -1.5)
MinVolt_Prox Minimum Input Volts (pk-neg), healthy Input, Prox -24 to -16
(default is -18.5)
MaxVolt_KP Maximum Input Volts (pk-neg), healthy Input, Keyphasor -4 to 0
(default is -1.5)
MinVolt_KP Minimum Input Volts (pk-neg), healthy Input, Keyphasor -24 to -16
(default is -22.0)
MaxVolt_Seis Maximum Input Volts (pk-pos),healthy Input,Seismic:Values > 1.25 require
use of GnBiasOvride
0 to 2.75
(default is 1.0)
MinVolt_Seis Minimum Input Volts (pk-neg),healthy Input,Seismic:Values < -1.25 require
use of GnBiasOvride
-2.75 to 0
(default is -1.0)
MaxVolt_Acc Maximum Input Volts (pk),healthy Input,Accel -12 to 1.5
(default is -8.5)
MinVolt_Acc Minimum Input Volts (pk-neg),healthy Input,Accel -24 to -1
(default is -11.5)
MaxVolt_Vel Maximum Input Volts (pk),healthy Input,Velomitor -12 to 1.5
MinVolt_Vel Minimum Input Volts (pk-neg),healthy Input,Velomitor -24 to -1
MaxVolt_CDM_BN Maximum Input Volts (pk),healthy Input,CDM Bently Nevada -12 to 24
MinVolt_CDM_BN Minimum Input Volts (pk-neg),healthy Input,CDM Bently Nevada -24 to 12
MaxVolt_CDM_PCB Maximum Input Volts (pk),healthy Input,CDM PCB -12 to 24
MinVolt_CDM_PCB Minimum Input Volts (pk-neg),healthy Input,CDM PCB -24 to 12
CDM_Scan_Period The scan period for CDM sensor inputs in seconds
Only assign as 0.01 increments
0.01 to 2.0
262 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Table of Contents

Related product manuals