2690-2721
Description IOPoint [ ] - Shorted field wire detected
Possible Cause A short circuit has been detected at the terminal board, based on the sensor type.
Solution Digital Input:
Check the wiring between the terminal board and the device.
Verify that the recommended line monitoring resistors are being used (refer to the I/O pack user documentation).
2722-2753
Description IOPoint [ ] - NAMUR Sensor Failure detected
Possible Cause Detected NAMUR sensor operation is outside its two normal current levels (between 1.0 mA and 2.2
mA)
Solution Digital Input:
Check the wiring between the terminal board and the sensor.
Check the sensor for proper operation.
Replace the NAMUR device.
2754-2785
Description IOPoint [ ] - Input Saturation detected
Possible Cause An internal component's valid input range was exceeded. This could be due to the following reasons:
Input signal equal to or exceeds the valid input range for the input type (improper sensor connected, sensor failure)
Open-circuit field wiring
Internal hardware failure
Solution
Current Input: check field wiring and verify that the input source is between -11 V and 20 V (or 80 mA).
Voltage Input:
For ± 5 V input, check field wiring and verify that the input source is between -11 V and 20 V.
For ± 10 V input, check field wiring and verify that the input source is between -11 V and 22 V.
RTD Input:
For MINCO_CA type, check for open circuits in the field wiring and then verify that the input source is between
-78.125 mV and 78.125 mV.
For all other RTD types, check field wiring and verify that the input source is between -1.25 V and 1.25 V.
TC Input: check field wiring and verify that the input source is between -625 mV and 625 mV.
Digital Input:
For externally wetted inputs, check field wiring and verify that the input source is between -11 V and 20 V.
For internally wetted inputs, check field wiring and verify input source is between -11 V and 20 V.
Pulse Accumulator (PA) Input: check field wiring and verify that the input source is between -11 V and 22 V.