340
Description Memory Verification failed - Data structures
Possible Cause Hardware memory failure (data that should not change after I/O pack or module has gone online has
been modified)
Solution
• Rebuild and download the application to all affected I/O packs or modules.
• Reload the firmware and application code.
• If problem persists, replace the I/O pack or module.
341
Note This alarm is obsolete.
Description Firmware or I/O Configuration Incompatibility
Possible Cause I/O pack or module configuration files incompatible with firmware (files do not contain necessary
revision)
Solution
• Confirm the correct installation of the ToolboxST software.
• Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
• Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
342
Description Firmware or Configuration Incompatible
Possible Cause I/O pack or module configuration files incompatible with firmware (files do not contain necessary
revision)
Solution
• Confirm the correct installation of the ToolboxST application.
• Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
• Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
343
Description Memory Verification failed - Firmware Libraries
Possible Cause Hardware memory failure (data that should not change after the I/O pack or module has gone online was
modified)
Solution
• Rebuild and download the application to all affected I/O packs or modules.
• Reload the firmware and application code.
• If the problem persists, replace the I/O pack or module.
464 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information