EasyManua.ls Logo

GE Mark VIeS - Memory Verification Failed - Data Structures; Firmware or I;O Configuration Incompatibility; Firmware or Configuration Incompatible; Memory Verification Failed - Firmware Libraries

GE Mark VIeS
486 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
340
Description Memory Verification failed - Data structures
Possible Cause Hardware memory failure (data that should not change after I/O pack or module has gone online has
been modified)
Solution
Rebuild and download the application to all affected I/O packs or modules.
Reload the firmware and application code.
If problem persists, replace the I/O pack or module.
341
Note This alarm is obsolete.
Description Firmware or I/O Configuration Incompatibility
Possible Cause I/O pack or module configuration files incompatible with firmware (files do not contain necessary
revision)
Solution
Confirm the correct installation of the ToolboxST software.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack or module and
selecting Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
342
Description Firmware or Configuration Incompatible
Possible Cause I/O pack or module configuration files incompatible with firmware (files do not contain necessary
revision)
Solution
Confirm the correct installation of the ToolboxST application.
Verify that each I/O pack or module is upgraded to the latest version by right-clicking each I/O pack and selecting
Upgrade.
Rebuild the application, and download the firmware and application code to the affected I/O pack or module.
343
Description Memory Verification failed - Firmware Libraries
Possible Cause Hardware memory failure (data that should not change after the I/O pack or module has gone online was
modified)
Solution
Rebuild and download the application to all affected I/O packs or modules.
Reload the firmware and application code.
If the problem persists, replace the I/O pack or module.
464 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II