Description Internal data transfer error - Expected ID [ ] Read ErrCntr/ID [ ]
Possible Cause There is an I/O pack failure or software process conflict that may be cleared by a hard reset.
Solution
Cycle power on the I/O pack.
Replace the I/O pack.
49
Description Internal hardware failure - Status [ ]
Possible Cause An I/O pack has failed.
Solution Replace the I/O pack.
50
Description Channel [ ] DC Isolation Test Failure
Possible Cause The I/O pack failed to auto-calibrate when powered on.
Solution Replace the I/O pack.
51
Description I/O pack processor failure - Status [ ]
Possible Cause The I/O pack failed.
Solution Replace the I/O pack.
52-64
Description TVBA Analog Input [ ] Open Circuit ([ ] Volts)
Possible Cause An open circuit has been detected on the terminal board based on the sensor type.
Solution
Check the wiring between the terminal board and the sensor.
Check the sensor for proper operation.
Replace the terminal board.
272 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II