374
Description Invalid Calibration Settings
Possible Cause
Calibration file not detected
Calibration file corrupted
Calibration constants invalid
Hardware Failure
Solution Replace the module.
375
Description Controller has entered Quality Control (QC) Mode
Possible Cause The device has received a command to enter factory QC mode.
Solution Reboot the device.
462
Description Hardware Reconfigured: Reboot by removing and reapplying power
Possible Cause Flash memory file system corruption.
Solution
After reapplying power, Rebuild and download baseload, firmware and application.
If the problem persists, replace the controller.
463
Description Internal runtime error - Could not create the Command and Event Log (CEL) file
Possible Cause Internal runtime error. Could not create the CEL file.
Solution
Rebuild and download baseload, firmware, and application to the controller.
If the problem persists, replace the controller.
464
Description Ethernet Interface [ ] disabled due to excessive traffic
Possible Cause Network interface has been disabled to protect itself from excessive activity on the network.
Solution
Check for network loops.
Monitor network activity and remove excessive traffic.
58 GEH-6855_Vol_II GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II