Description Incorrect or Missing Acquisition Board on HSSL link 2
Possible Cause The acquisition card on High Speed Serial Link 2 is not connected or does not agree with the ToolboxST
configuration.
Solution
Verify that the correct acquisition card is connected to the specified HSSL connector on the UCSA.
Verify that the ToolboxST configuration for the appropriate HSSL connector matches the hardware.
447
Description Incorrect or Missing Acquisition Board on HSSL link 3
Possible Cause The acquisition card on High Speed Serial Link 3 is not connected or does not agree with the ToolboxST
configuration.
Solution
Verify that the correct acquisition card is connected to the specified HSSL connector on the UCSA.
Verify that the ToolboxST configuration for the appropriate HSSL connector matches the hardware.
448
Description Acquisition Board barcode mismatch on HSSL link 1
Possible Cause The barcode on the acquisition card connected to High Speed Serial Link 1 does not agree with those
provided in the ToolboxST application
Solution Verify that the correct acquisition card is connected to the link and that the correct barcode has been entered in
the ToolboxST application
449
Description Acquisition Board barcode mismatch on HSSL link 2
Possible Cause The barcode on the acquisition card connected to High Speed Serial Link 2 does not agree with those
provided in the ToolboxST application
Solution Verify that the correct acquisition card is connected to the link and that the correct barcode has been entered in
the ToolboxST application
450
Description Acquisition Board barcode mismatch on HSSL link 3
Possible Cause The barcode on the acquisition card connected to High Speed Serial Link 3 does not agree with those
provided in the ToolboxST application
Solution Verify that the correct acquisition card is connected to the link and that the correct barcode has been entered in
the ToolboxST application
Common I/O Module Functionality GEH-6855_Vol_II System Guide 471